PID and Ziegler-Nichols Tuning
The three terms answer three different questions about the same error. Proportional asks how wrong am I - it acts at once and always leaves some error behind, because zero error would mean zero output. Integral asks how long have I been wrong - it keeps pushing until the error is gone, and it is the only cure for the droop Maxwell described in 1868. Derivative asks how fast is it changing - it is Sperry's rate term, damping the loop.
None of that was new in 1942. What John Ziegler and Nathaniel Nichols contributed at Taylor Instrument was a way to SET them without knowing anything about the process. Turn the proportional gain up, with the other two at zero, until the plant oscillates steadily; call that gain Ku and time the swings to get Tu. Then read six numbers off a table: for a full three-term controller, Kp is 0.6 Ku, the integral time is Tu over 2 and the derivative time is Tu over 8. A plant engineer with a stopwatch and no model could tune a loop in an afternoon, and eighty years later most of the loops running in the physical world were still set that way.
It is worth knowing what the table is aiming at, because it is aggressive. Ziegler and Nichols targeted quarter-amplitude damping - each swing a quarter of the one before - which recovers from an upset quickly and overshoots hard on the way. That is right for a process that must shrug off disturbances and quite wrong wherever overshoot is expensive, so every handbook since has published gentler variants of the same six numbers.
Two things the equation does not mention will decide whether your loop works. The derivative term differentiates the sensor's noise as happily as the signal, and the integral term keeps accumulating while the heater is already flat out - which is why a controller without anti-windup is not a PID controller but a PID controller with a fault.
মধ্যবর্তী
4 hours
নির্দেশ
1
1
A plant with a real dead time
A plant with a real dead time
Bolt a 10 W power resistor to one end of a short aluminium bar and press the thermistor into a hole at the other end, with a smear of thermal paste in both.
That gap is the point. Switch the heater on and time how long it takes the thermistor to move at all - several seconds of pure dead time, which is what makes this loop hard and what a bare thermistor on the resistor would hide.
ইস চরণ কে লিএ সামগ্রী:
Aluminum Bar Stock150 mm
Power Resistor Kit - 10W (25 pack)1 কিট
NTC Thermistor Kit (50pcs, 10 Values)1 কিট
Thermal Paste (Arctic Silver, 3.5g)1 tubeআবশ্যক উপকরণ:
Cordless Drill
Stopwatch
Digital Multimeter (Lab Grade)
Bench Power Supply (30V/5A)2
2
The controller, with the two lines nobody mentions
The controller, with the two lines nobody mentions
One constant selects on/off, P, PI or PID; the gains come from Ku and Tu through the Ziegler-Nichols table.
Measure Ku and Tu on YOUR block first - raise Kp with the other terms at zero until the temperature swings steadily, then time it. Run all four modes and you have the notebook's table in your own hardware.
pid_heater.inocpp
ইস চরণ কে লিএ সামগ্রী:
IRF540N N-Channel MOSFET (10-Pack)1 প্যাক
1/4W Resistor Kit (600pcs, 30 Values)1 কিট
Dupont Jumper Wire Set (M-F, 40-Way)1 সেটআবশ্যক উপকরণ:
Arduino Uno R3 SMD
Breadboard - Classic
Desktop Computer
Bench Power Supply (30V/5A)3
3
Ku, Tu, the table, and four controllers compared
Ku, Tu, the table, and four controllers compared
Loading Jupyter Notebook...
আবশ্যক উপকরণ:
Desktop Computer4
4
Compendium: the other method, and what Ku costs to find
Compendium: the other method, and what Ku costs to find
Ziegler and Nichols published two methods and the one everybody quotes is the harder one to use. Finding Ku means deliberately driving a live process into sustained oscillation, which on a chemical plant, a furnace or anything with a safety case is not a reasonable thing to do. Their open-loop method avoids it entirely: put a step into the plant with the controller off, draw a tangent at the steepest point of the response curve, and read off the apparent dead time L and the slope R. The gains follow from those two numbers alone - for a PID, Kp is 1.2 over R L, the integral time is 2 L and the derivative time is 0.5 L - and the plant is never asked to misbehave.
Both methods are really estimating the same thing, which is how much phase the plant spends before its gain runs out. That is Nyquist's question from ten years earlier, and the ultimate-sensitivity experiment measures the answer directly: at the point of steady oscillation the loop gain is exactly one and the phase exactly minus 180 degrees, so Ku and Tu ARE the coordinates of the critical point. The 1942 table is Nyquist's criterion reformulated as something you can do with a knob and a stopwatch, which is why it spread through industries that never read the 1932 paper.
আবশ্যক উপকরণ:
Notebook and Pencilসামগ্রী
7- Aluminum Bar Stock10% কমীশন150 mmপ্লেসহোল্ডর
- Power Resistor Kit - 10W (25 pack)10% কমীশন1 কিট$6.00
- NTC Thermistor Kit10% কমীশন1 কিটপ্লেসহোল্ডর
- প্লেসহোল্ডর
- IRF540N N-Channel MOSFET10% কমীশন1 প্যাকপ্লেসহোল্ডর
- 1/4W Resistor Kit10% কমীশন1 কিটপ্লেসহোল্ডর
- Dupont Jumper Wire Set (M-F)100% কমীশন1 সেটপ্লেসহোল্ডর
আবশ্যক উপকরণ
8- Cordless Drill10% কমীশনপ্লেসহোল্ডর
- Digital Multimeter - Lab Grade10% কমীশনপ্লেসহোল্ডর
- প্লেসহোল্ডর
- Arduino Uno R3 SMD10% কমীশন$27.00
- Breadboard - Classic10% কমীশন$10.00
- Desktop Computer100% কমীশনপ্লেসহোল্ডর
- Notebook and Pencil10% কমীশনপ্লেসহোল্ডর
আনুমানিক মোট
$6.00সম্পর্কিত ব্লুপ্রিন্ট
এই ব্লুপ্রিন্টগুলি জ্ঞান ভাগ করে — কৌশল, উপকরণ বা নীতি
CC0 পব্লিক ডোমেন
যহ ব্লূপ্রিংট CC0 কে তহত জারী কিযা গযা হৈ। আপ বিনা অনুমতি মাঁগে ইস কার্য কো কিসী ভী উদ্দেশ্য কে লিএ কॉপী, সংশোধিত, বিতরিত ঔর উপযোগ করনে কে লিএ স্বতংত্র হৈং।
উনকে ব্লূপ্রিংট কে মাধ্যম সে উত্পাদ খরীদকর মেকর কা সমর্থন করেং জহাঁ বে মেকর কমীশন কমাতে হৈং জো বিক্রেতাওং দ্বারা নির্ধারিত হোতা হৈ, যা ইস ব্লূপ্রিংট কা নযা সংস্করণ বনাএঁ ঔর রাজস্ব সাঝা করনে কে লিএ ইসে অপনে ব্লূপ্রিংট মেং কনেক্শন কে রূপ মেং শামিল করেং।