NGHỆ THUẬT
LÀM ĐẸP VÀ SỨC KHỎE
THỦ CÔNG
VĂN HÓA VÀ LỊCH SỬ
GIẢI TRÍ
MÔI TRƯỜNG
THỰC PHẨM VÀ ĐỒ UỐNG
KỸ THUẬT NGƯỢC
KHOA HỌC
THỂ THAO
CÔNG NGHỆ
THIẾT BỊ ĐEO

PID and Ziegler-Nichols Tuning
The three terms answer three different questions about the same error. Proportional asks how wrong am I - it acts at once and always leaves some error behind, because zero error would mean zero output. Integral asks how long have I been wrong - it keeps pushing until the error is gone, and it is the only cure for the droop Maxwell described in 1868. Derivative asks how fast is it changing - it is Sperry's rate term, damping the loop.
None of that was new in 1942. What John Ziegler and Nathaniel Nichols contributed at Taylor Instrument was a way to SET them without knowing anything about the process. Turn the proportional gain up, with the other two at zero, until the plant oscillates steadily; call that gain Ku and time the swings to get Tu. Then read six numbers off a table: for a full three-term controller, Kp is 0.6 Ku, the integral time is Tu over 2 and the derivative time is Tu over 8. A plant engineer with a stopwatch and no model could tune a loop in an afternoon, and eighty years later most of the loops running in the physical world were still set that way.
It is worth knowing what the table is aiming at, because it is aggressive. Ziegler and Nichols targeted quarter-amplitude damping - each swing a quarter of the one before - which recovers from an upset quickly and overshoots hard on the way. That is right for a process that must shrug off disturbances and quite wrong wherever overshoot is expensive, so every handbook since has published gentler variants of the same six numbers.
Two things the equation does not mention will decide whether your loop works. The derivative term differentiates the sensor's noise as happily as the signal, and the integral term keeps accumulating while the heater is already flat out - which is why a controller without anti-windup is not a PID controller but a PID controller with a fault.
Trung cấp
4 hours
Hướng dẫn
1
1
A plant with a real dead time
A plant with a real dead time
Bolt a 10 W power resistor to one end of a short aluminium bar and press the thermistor into a hole at the other end, with a smear of thermal paste in both.
That gap is the point. Switch the heater on and time how long it takes the thermistor to move at all - several seconds of pure dead time, which is what makes this loop hard and what a bare thermistor on the resistor would hide.
Vật liệu cho bước này:
Aluminum Bar Stock150 mm
Power Resistor Kit - 10W (25 pack)1 bộ
NTC Thermistor Kit (50pcs, 10 Values)1 bộ
Thermal Paste (Arctic Silver, 3.5g)1 tubeCông cụ cần thiết:
Cordless Drill
Stopwatch
Digital Multimeter (Lab Grade)
Bench Power Supply (30V/5A)2
2
The controller, with the two lines nobody mentions
The controller, with the two lines nobody mentions
One constant selects on/off, P, PI or PID; the gains come from Ku and Tu through the Ziegler-Nichols table.
Measure Ku and Tu on YOUR block first - raise Kp with the other terms at zero until the temperature swings steadily, then time it. Run all four modes and you have the notebook's table in your own hardware.
pid_heater.inocpp
Vật liệu cho bước này:
IRF540N N-Channel MOSFET (10-Pack)1 gói
1/4W Resistor Kit (600pcs, 30 Values)1 bộ
Dupont Jumper Wire Set (M-F, 40-Way)1 bộCông cụ cần thiết:
Arduino Uno R3 SMD
Breadboard - Classic
Desktop Computer
Bench Power Supply (30V/5A)3
3
Ku, Tu, the table, and four controllers compared
Ku, Tu, the table, and four controllers compared
Loading Jupyter Notebook...
Công cụ cần thiết:
Desktop Computer4
4
Compendium: the other method, and what Ku costs to find
Compendium: the other method, and what Ku costs to find
Ziegler and Nichols published two methods and the one everybody quotes is the harder one to use. Finding Ku means deliberately driving a live process into sustained oscillation, which on a chemical plant, a furnace or anything with a safety case is not a reasonable thing to do. Their open-loop method avoids it entirely: put a step into the plant with the controller off, draw a tangent at the steepest point of the response curve, and read off the apparent dead time L and the slope R. The gains follow from those two numbers alone - for a PID, Kp is 1.2 over R L, the integral time is 2 L and the derivative time is 0.5 L - and the plant is never asked to misbehave.
Both methods are really estimating the same thing, which is how much phase the plant spends before its gain runs out. That is Nyquist's question from ten years earlier, and the ultimate-sensitivity experiment measures the answer directly: at the point of steady oscillation the loop gain is exactly one and the phase exactly minus 180 degrees, so Ku and Tu ARE the coordinates of the critical point. The 1942 table is Nyquist's criterion reformulated as something you can do with a knob and a stopwatch, which is why it spread through industries that never read the 1932 paper.
Công cụ cần thiết:
Notebook and PencilVật liệu
7- Aluminum Bar StockHoa hồng 10%150 mmTạm thời
- Power Resistor Kit - 10W (25 pack)Hoa hồng 10%1 bộ$6.00
- NTC Thermistor KitHoa hồng 10%1 bộTạm thời
- Tạm thời
- IRF540N N-Channel MOSFETHoa hồng 10%1 góiTạm thời
- 1/4W Resistor KitHoa hồng 10%1 bộTạm thời
- Dupont Jumper Wire Set (M-F)Hoa hồng 100%1 bộTạm thời
Công cụ yêu cầu
8- Cordless DrillHoa hồng 10%Tạm thời
- Digital Multimeter - Lab GradeHoa hồng 10%Tạm thời
- Tạm thời
- Arduino Uno R3 SMDHoa hồng 10%$27.00
- Breadboard - ClassicHoa hồng 10%$10.00
- Desktop ComputerHoa hồng 100%Tạm thời
- Notebook and PencilHoa hồng 10%Tạm thời
Tổng ước tính
$6.00Blueprint liên quan
Các blueprint này chia sẻ kiến thức — kỹ thuật, vật liệu hoặc nguyên tắc
CC0 Phạm vi công cộng
Bản thiết kế này được phát hành theo CC0. Bạn tự do sao chép, sửa đổi, phân phối và sử dụng cho bất kỳ mục đích nào mà không cần xin phép.
Hỗ trợ nhà sáng tạo bằng cách mua sản phẩm qua bản thiết kế, nơi họ nhận Hoa hồng nhà sáng tạo do nhà bán hàng đặt, hoặc tạo phiên bản mới và kết nối trong bản thiết kế riêng để chia sẻ doanh thu.