The Contactor: A Relay That Remembers to Stay Off
A motor's supply is too heavy for a hand switch to make and break safely, and a machine that starts by itself when the power returns can kill. The contactor answers both: a heavy relay whose main contacts switch the motor, controlled by a start button, a stop button and one of its own auxiliary contacts that holds it in once started.
That one extra contact — the seal-in — turns the relay into a memory. Press Start and it latches. Press Stop, or lose the supply for a moment, and it drops out and stays out until someone presses Start again. The same circuit, with an overload relay added, is the motor starter on almost every machine.
This rung simulates two- and three-wire control through a power cut, works out why a contactor holds at a lower voltage than it needs to pull in, and wires a working start/stop station on the bench.
Pemula
About 3 hours
Arahan
1
1
Seal-in logic, power cuts and pull-in voltage
Seal-in logic, power cuts and pull-in voltage
Memuatkan buku nota Jupyter…
2
2
The start/stop station, step by step
The start/stop station, step by step
Ruang Kerja Blockly
Loading Blockly workspace...
3
3
The seal-in is an OR with memory
The seal-in is an OR with memory
Start OR seal-in, AND NOT Stop: the starter is relay logic. The embedded blueprint builds the gates it is made of.
4
4
Wire a start/stop station at 12 V
Wire a start/stop station at 12 V
Use a 12 V relay with a changeover contact as the contactor: its coil is the contactor coil, one contact carries the load, and — for the seal-in — use a second relay driven from the same coil supply, or a relay with two sets of contacts.
Wire, from the 12 V supply: the **Stop** button (normally closed) → then **Start** (normally open) and the seal-in contact in parallel → the relay coil → 0 V. Wire the load contact to a geared DC motor through its own fused 12 V feed.
Press Start: the motor runs and keeps running when you let go. Press Stop: it stops. Start it again, then switch the power supply off and on: it stays stopped. Now remove the seal-in wire and wire a toggle switch in place of Start and Stop — two-wire control — and repeat the power cut: this time it restarts by itself.
Bahan untuk langkah ini:
Geganti SPDT2 keping
Butang tekan2 keping
Motor DC bergear1 keping
Wayar Pelompat1 keping
Pemegang fius AT1 keping
Kontaktor1 kepingAlatan diperlukan:
Unit kuasa arus terus
Multimeter
Alat pematerian
Wayar Ujian Berpenyepit Buaya5
5
A starter that will not start or will not stay in
A starter that will not start or will not stay in
Motor starter faults, from the control circuit outwards.
Flow
Loading...
6
6
Context and honest limits
Context and honest limits
Magnetic motor starters with start and stop push buttons and a hold-in contact became the standard way to control industrial motors in the first half of the twentieth century, and the three-wire circuit is still drawn the same way in every motor-control manual.
**Honest limits.** A 12 V relay shows the logic, not the job: a real contactor's main contacts must break motor current, and mains and three-phase supplies must be wired only by someone qualified to do it. The pull-in figures in the notebook use the same air-gap-only magnet model as the solenoid valve and overstate the pull.
Bahan
6- 2 kepingPemegang Tempat
- dari$0.51
- dari$2.53
- dari$1.60
- 1 kepingPemegang Tempat
- 1 kepingPemegang Tempat
Alatan Diperlukan
4- Pemegang Tempat
- Pemegang Tempat
- Alat pematerian10% komisenMagento Legacy Storeships internationallyPemegang Tempat
- Pemegang Tempat
Blueprint berkaitan
Blueprint ini berkongsi pengetahuan — teknik, bahan atau prinsip
CC0 Domain Awam
Blueprint ini dikeluarkan di bawah CC0. Anda bebas menyalin, mengubah, mengedar, dan menggunakan karya ini untuk sebarang tujuan, tanpa meminta kebenaran.
Sokong Pembuat dengan membeli produk melalui Blueprint mereka di mana mereka memperoleh Komisen Pembuat ditetapkan oleh Penjual, atau cipta iterasi baru Blueprint ini dan sertakan ia sebagai sambungan dalam Blueprint anda sendiri untuk berkongsi hasil.