The Contactor: A Relay That Remembers to Stay Off
Volt

Tạo bởi

Volt

27. tháng Chín 2026SE
6
0
0
0
0

The Contactor: A Relay That Remembers to Stay Off

A motor's supply is too heavy for a hand switch to make and break safely, and a machine that starts by itself when the power returns can kill. The contactor answers both: a heavy relay whose main contacts switch the motor, controlled by a start button, a stop button and one of its own auxiliary contacts that holds it in once started. That one extra contact — the seal-in — turns the relay into a memory. Press Start and it latches. Press Stop, or lose the supply for a moment, and it drops out and stays out until someone presses Start again. The same circuit, with an overload relay added, is the motor starter on almost every machine. This rung simulates two- and three-wire control through a power cut, works out why a contactor holds at a lower voltage than it needs to pull in, and wires a working start/stop station on the bench.
Cơ bản
About 3 hours

Hướng dẫn

1

Seal-in logic, power cuts and pull-in voltage

Đang tải sổ tay Jupyter…
2

The start/stop station, step by step

Không gian làm việc Blockly

Loading Blockly workspace...

3

The seal-in is an OR with memory

Start OR seal-in, AND NOT Stop: the starter is relay logic. The embedded blueprint builds the gates it is made of.
4

Wire a start/stop station at 12 V

Use a 12 V relay with a changeover contact as the contactor: its coil is the contactor coil, one contact carries the load, and — for the seal-in — use a second relay driven from the same coil supply, or a relay with two sets of contacts. Wire, from the 12 V supply: the **Stop** button (normally closed) → then **Start** (normally open) and the seal-in contact in parallel → the relay coil → 0 V. Wire the load contact to a geared DC motor through its own fused 12 V feed. Press Start: the motor runs and keeps running when you let go. Press Stop: it stops. Start it again, then switch the power supply off and on: it stays stopped. Now remove the seal-in wire and wire a toggle switch in place of Start and Stop — two-wire control — and repeat the power cut: this time it restarts by itself.

Vật liệu cho bước này:

Rơ le SPDTRơ le SPDT2 cái
Nút nhấnNút nhấn2 cái
Động cơ một chiều có hộp sốĐộng cơ một chiều có hộp số1 cái
Dây nốiDây nối1 cái
Đế cầu chì một chiềuĐế cầu chì một chiều1 cái
Công tắc tơCông tắc tơ1 cái

Công cụ cần thiết:

Nguồn điện một chiềuNguồn điện một chiều
Đồng hồ vạn năngĐồng hồ vạn năng
Mỏ hànMỏ hàn
Dây thử có kẹp cá sấuDây thử có kẹp cá sấu
5

A starter that will not start or will not stay in

Motor starter faults, from the control circuit outwards.

Flow

Loading...
6

Context and honest limits

Magnetic motor starters with start and stop push buttons and a hold-in contact became the standard way to control industrial motors in the first half of the twentieth century, and the three-wire circuit is still drawn the same way in every motor-control manual. **Honest limits.** A 12 V relay shows the logic, not the job: a real contactor's main contacts must break motor current, and mains and three-phase supplies must be wired only by someone qualified to do it. The pull-in figures in the notebook use the same air-gap-only magnet model as the solenoid valve and overstate the pull.